А3795, ВА3795, А3735
SALE AND PRODUCTION OF AUTOMATIC SWITCHES VA3795, VA3795NU3, A3795BR, A3795BT3, A3795BHL3, A3735 ON NOMINAL CURRENT 630 A WITH ELECTROMAGNETIC REFERENCE SYSTEMS.
A3795NU3, VA3795, A3795BR, A3795BT3, A3795BHL3, A3735 circuit breakers are designed to conduct current in normal mode and to selectively protect against short circuits, overloads of unacceptable duration and unacceptable voltage drops, as well as for infrequent (up to 30 times a day) electrical outages circuits with a rated voltage up to 660 V AC, frequency 50 and 60 Hz.
The switches can be equipped with an independent release, zero voltage release, free contacts and an electromagnetic drive.
Switches are available in fixed and retractable versions.
Technical characteristics of switches:
1. Rated current A 800
2. Application category A.
3. The number of poles 2.
4. Rated current of a semiconductor tripping device (RP), A 250; 400; 630, 800.
5. Adjustable values of nominal operating currents IR, A 160; 200; 250. 250; 315; 400. 400; 500; 630; 800
6. The initial current of operation in the zone of overload currents, a multiple of the nominal operating current RP 1,25.
7. Setting the response time in the zone of overload currents at a current of 6IR, s: 4; eight; sixteen.
8. The settings for the operation current in the area of short-circuit currents, multiples of the rated operating current 2; 3; five; 7; ten.
9. Settings for the current operation of electromagnetic releases, A 4000; 6300.
10. Rated operating maximum breaking capacity, kA:
- at rated voltage 380 V 56.
- at a rated voltage of 660 V 27.
11. Wear resistance of switches:
- total number of cycles per 12000.
- the number of VO cycles under load 8000.
12. Overall dimensions (width x height x depth), mm 225x400x160.
13. Weight (stationary version), not more than 19.2 kg.
With electromagnetic drive 26.4 kg