Circuit breaker А 3713
SALE AND MANUFACTURE OF AUTOMATIC SWITCHES ВА3713, ВА3713Б, ВА3713БХЛ3, ВА3713БР, ВА3713БТ3 220V, 440V, 110V, 24V DC - AT RATED CURRENTS UP TO 32A-250 A WITH SEMICONDUCTOR COUPLERS. Exports the circuit breaker VA 3713 in Europe, Asia and Africa.
Technical description: A3710 circuit-breakers for rated current up to 160 A and VA3710 nom. current up to 200A with semiconductor, thermal and electromagnetic releases. Circuit breakers VA3711, VA3713, VA3715, VA3717- 2 poles are manufactured for constant and alternating currents (Hz 50, 400). Automatic switches ВА3712, ВА3714, ВА3716, ВА3718 - 3 pole, are made on alternating current (Hz 50, 400). Automatic circuit breakers are designed to conduct current in normal mode and protect against overloads of unacceptable duration, with short circuits and unacceptable voltage drops, and for infrequent, up to 30 times a day, operational tripping of electrical circuits with a rated voltage of up to 660 VAC of frequency 50 and 60 Hz and up to 440 VDC. AC automatic circuit breakers can also be used for protection and infrequent direct starts of asynchronous motors in the application category of AC-3. Circuit-breakers are manufactured with semiconductor releases, with semiconductor and electromagnetic maximum releases, with thermal and electromagnetic maximum current releases, only with electromagnetic maximum current releases and without maximum current releases. The circuit breakers can be equipped with a zero-voltage release, an independent release, free contacts and an electromagnetic drive. Circuit-breakers are available in stationary version - front, rear and combined connection and in retractable design.
Switches are manufactured in stationary and in retractable designs.
Switches can be equipped with an independent release, a zero-voltage release, free contacts, an electromagnetic drive, a manual remote drive (in retractable version).
The main technical characteristics of the switches:
1. Rated current, A 200
2. Application category V.
3. Rated currents of semiconductor releases (RP), A 80; 160; 200; 250.
4. Adjustable values of rated working currents IR, A:
- 16; 20; 25; 31.5; 40; 50; 63; 70; 80;
- 80; 90; 100; 110; 120; 125; 140; 150; 160; 200; 250.
5. Initial operating current in the zone of overcurrent currents, multiples of the rated working current of RP 1.25.
6. Set-point according to the response time in the overload current zone, s: 1; 2; 4 at a current of 5IR or 2; 4; 8; 16 at a current of 6IR.
7. Settings for the response time in the zone of short-circuit currents, c 0; 0.1; 0.2; 0.3 (also available with settings of 0.4 and 0.5 s).
8. Settings for the operating current in the zone of short-circuit currents, multiples of the rated working current 2; 3; 5; 7; 9; 10.
9. Rated short-time withstand current, kA 5.
10. Rated operating short-circuit breaking capacity, kA 7.5.
11. Wear resistance of switches:
a) the total number of cycles is 16,000.
b) number of cycles of VO under load:
- switches for rated current 80 A 10000.
- switches for rated current 160 A 8000.
12. Overall dimensions (width x height x depth), mm 112x320x157.
13. Weight (stationary version), not more than, 7.0 kg. With electromagnetic drive - 9.5 kg.