Circuit breaker AVM4SVU3-AVM4S
We selling and production the automatic circuit breakers AVM4SV-U3 withdrawable version and AVM4S-U3 stationary for 500V, 380 V 400V 50-60 Hz - 400A, 300A, 250A, 200A, 150A, 100A, 120A, 500 A. Automatic switches AVM4SV, AV4SV, AV4S, AVM 4SV, AVM4SM-U3 and AVM10S have been successfully operated for 50 years in substations of plants in Ukraine, Turkey, Moldova, Azerbaijan, Albania, Kazakhstan, Latvia, Estonia, Lithuania, Armenia, Georgia, Uzbekistan, Kirghizia, Iraq, Mongolia, Montenegro, Turkmenistan, Romania, Bulgaria, Poland, Czech Republic, Tajikistan, Mongolia, Montenegro, Macedonia, Slovenia, Slovakia, Serbia, as well as in other Europe and Asia. Selling the circuit breaker AV4SV, AV4SM with electromagnetic drive. Sale. Export AVM 4SV, AVM4S. Buy the switch ABM4CB-Y3, ABM4C-Y3, ABM4CM for 100 A, 120 A, 150 A, 200 A, 250 A, 300 A, 400 A, 500A, 600A. We sell the breakers AV4SV 600V 50Hz. Best price on circuit breaker AVM type 500V 400A, 300A TU16-522.010-73.
Technical description: AVM4 circuit breakers are manufactured by electromagnetic releases and releases for tripping from overload. Automatic switches АВМ4 2-pole are made on a direct current. Automatic switches АВМ4 3-pole, are made on an alternating current. АВМ4С - selective circuit breakers (with a delay of operation on time)
AVM4S circuit breakers are designed to conduct current in normal mode and protect against overloads of unacceptable duration, short circuits and unacceptable voltage drops, and for infrequent, up to 20 times a day, operational tripping of electrical circuits with a rated voltage of up to 660 V AC frequency 50 and 60 Hz and up to 440 VDC. AC automatic circuit breakers can also be used for protection and infrequent direct starts of asynchronous motors in the application category of AC-3. Circuit-breakers are produced by thermal and electromagnetic maximum releases, only with electromagnetic maximum current releases and without maximum current releases. The circuit breakers can be equipped with a minimum voltage release, an independent release, free contacts and an electromagnetic drive. Automatic are produced in a stationary version - front, rear and combined connection and in retractable design.
Technical characteristics of the switches:
1. Rated current 400A.
2. Number of poles 2; 3.
3. Rated currents of the releases from overload- up to 100, 120, 150, 200, 300, 400 A.
4. The setting for the initial pick-up current in the zone of the overload currents, a multiple of the rated current of the thermal release 1.25.
5. Settings for the current tripping of electromagnetic maximum current releases up to 4000A.
6. Rated operating short-circuit breaking capacity, kA: at a rated voltage of 380 V AC 25, at a nominal voltage of 660 V AC 19, at a nominal voltage of 440 VDC 50.
7. Wear resistance of circuit breakers - total number of cycles of VO 3000, number of VO cycles under load 1500.
8. Weight - up to 49 kg.