Circuit breaker AVM15NV, AVM15N
Buy and manufacturing of circuit breakers AVM15NV-U3 drawout and AVM15N-U3 stationary for 500V 1500A, 1200A, 1000A. Automatic circuit breakers ABM15H, ABM15HB, AVM15NV, AVM-15NV, AVM15NV-U3, AVM15NT3, AV15N, AV15NV and AVM15N ~500 V, 400 V, 380V AC/DC have been successfully operated for 50 years in substations of factories in Ukraine, Turkey, Azerbaijan, Kazakhstan, Latvia, Estonia, Lithuania, Armenia, Kyrgyzstan, Uzbekistan, Turkmenistan, Kyrgyzstan, Georgia, Moldova, Bulgaria, Romania, Poland, Mongolia, Czech Republic, Montenegro, Slovenia, Slovakia, Serbia, Bosnia, Herzegovina, Tajikistan, Vietnam, as well as in other countries of Europe and Asia. Best price on Circuit breaker AVM type 500V 1000A, 1150A, 1200A TU16-522.010-73. Exports, service, repair, spare parts. Warranty. We sell automatic circuit breaker ABM15HB, ABM15H - sale. Selling automatic circuit breaker AVM15N 1150A, 1200A, 1000A, 1500A =440V DC.
Technical description: AVM15N automatic circuit breakers are manufactured by electromagnetic releases and tripping devices for tripping from overload. Automatic switches AVM15N 2 poles are made on a direct current. Automatic switches АВМ15Н 3х polar, are made on an alternating current. AVM15N-nonselective automatic switches (high-speed)
AVM15N automatic circuit breakers are designed to conduct current in normal mode and protect against overloads of unacceptable duration, short circuits and unacceptable voltage drops, as well as for infrequent, up to 20 times a day, operational tripping of electrical circuits with a rated voltage of up to 660 V AC frequency 50 and 60 Hz and up to 440 VDC. AC automatic circuit breakers can also be used for protection and infrequent direct starts of asynchronous motors in the application category of AC-3. Circuit-breakers are produced by thermal and electromagnetic maximum releases, only with electromagnetic maximum current releases and without maximum current releases. The circuit breakers can be equipped with a minimum voltage release, an independent release, free contacts and an electromagnetic drive. Automatic are produced in a stationary version - front, rear and combined connection and in retractable design.
Technical characteristics of AVM15H switches:
1. Rated current: fixed version is 1500A, withdrawable version is 1200A.
2. Number of poles 2; 3.
3. Rated current of releases from overloads - up to 1500A.
4. Setting for the initial pick-up current in the zone of the overload currents, multiples of the rated current of the thermal trip unit 1.3.
5. Settings for the current of operation of electromagnetic maximum current releases up to 9000A.
6. Rated operating short-circuit breaking capacity, kA: at a rated voltage of 380 V AC 25, at a nominal voltage of 660 V AC 19, at a nominal voltage of 440 VDC 50.
7. Wear resistance of circuit breakers - total number of cycles of VO 3000, number of VO cycles under load 1500.
8. Weight - up to 118 kg.